| Specifications |
| Voltage DC |
Maximum voltage |
1000 V |
| Accuracy |
±(0.2%+2) |
| Maximum resolution |
0.001 V |
| Voltage AC |
Maximum voltage |
1000 V |
| Accuracy |
±(2%+3) |
| Maximum resolution |
0.1 mV |
| Current DC |
Maximum amps |
400 mA |
| Amps accuracy |
±(1.0%+2) |
| Maximum resolution |
0.01 mA |
| Current AC |
Maximum amps |
400 mA |
| Amps accuracy |
±(2.0%+2)* |
| Maximum resolution |
0.01 mA |
| Resistance |
Maximum resistance |
50 MΩ |
| Accuracy |
±(1.2%+2) |
| maximum resolution |
0.1Ω |
| Insulation Test |
| Minimum test current @ 1kΩ/V |
1 mA |
| Test voltages |
500, 1000 V |
| Maximum resistance per test voltage |
50 V |
|
| 100 V |
|
| 250 V |
|
| 500 V |
|
| 1000 V |
600 MΩ |
| Maximum resolution per test voltage |
50 V |
0.01 MΩ |
| 100 V |
0.01 MΩ |
| 250 V |
0.1 MΩ |
| 500 V |
0.1 MΩ |
| 1000 V |
0.1 MΩ |
| Accuracy per test voltage |
50 V |
±(3% + 5) |
| 100 V |
±(3% + 5) |
| 250 V |
±(1.5% + 5) |
| 500 V |
±(2.0% + 5) |
| 1000 V |
±(2.0% + 5) |
| Environmental Specifications |
| Operating temperature |
–20°C to +55°C |
| Storage temperature |
-40°C to +60°C |
| Humidity (without condensation) |
0% - 95% (10°C – 30°C) 0% - 75% (30°C – 40°C) 0% - 40% (40°C – 55°C) |
| Operating altitude |
2000 m |
| Safety Specifications |
| General |
IEC 61010-1: Pollution Degree 2 |
| Measurement |
IEC 61010-2-033: CAT IV 600V / CAT III 1000V |
| Mechanical and General Specifications |
| Size |
203 x 100 x 50 mm (with holster) |
| Weight |
624 g |
| Warranty |
3 years |
| Battery life alkaline |
Meter use |
1000 hours |
| Insulation test use |
Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
| IP rating |
IP40 |